top of page

Acrel Meter Selection Guide for Generator and Mains Monitoring

1 day ago
10 min read

A meter that looks right on a panel drawing can still be wrong for the job. Generator and mains monitoring need clear choices on voltage, current, supply, communications, and energy direction. If those details are vague, the result can be missing data, incorrect readings, or a meter that cannot connect to the wider system.


This guide helps buyers prepare a clear specification for ProSense Instruments when selecting an Acrel meter for generator and mains monitoring. The focus is monitoring, not generator control. The meter measures and reports electrical values. It does not start the generator, synchronise sets, open breakers, or replace a generator controller.


Wide-angle view of an electrical switchboard with generator and mains metering compartments
A clear metering layout starts with knowing what must be measured.

Monitoring and control are not the same task


Generator systems often combine several devices. A generator controller handles engine start, shutdown, alarms, breaker logic, and sometimes synchronising. A protection relay may trip a breaker during a fault. A power meter records values such as voltage, current, power, power factor, frequency, and energy.


An Acrel meter fits into the measurement and reporting part of that system. It can support operators, energy managers, BMS platforms, SCADA systems, and maintenance teams by showing what is happening electrically.


A monitoring meter can usually help answer questions such as:


  • What voltage is present on the generator or mains incomer?

  • How much current is flowing on each phase?

  • What is the real power demand?

  • Is power factor leading or lagging?

  • How much energy has been imported or exported?

  • Is frequency within the expected range?

  • Can the data be sent to another system by Modbus, Ethernet, or another supported method?


It should not be specified as if it were a generator control unit. If the requirement includes automatic start, load transfer, breaker closing, synchronising, load sharing, or engine protection, state that separately. Those functions need the correct control and protection equipment.


For a meter specification, keep the wording direct:


Supply and configure an Acrel meter for electrical monitoring of the generator incomer and mains incomer. Generator control, breaker control, and synchronising functions are excluded unless specified under separate equipment.

That single sentence can prevent a lot of confusion during pricing, design, and commissioning.


Start with the electrical system being monitored


The first part of an Acrel Meter Selection Guide for Generator and Mains Monitoring is the supply arrangement. A meter can only be selected correctly when the electrical system is clear.


Confirm the phase and wiring arrangement


Most generator and mains monitoring projects involve one of these arrangements:


Supply arrangement

What to specify

Why it matters

Single phase two wire

Line and neutral voltage

The meter must suit single phase measurement

Three phase three wire

Phase to phase voltage, no neutral reference

The meter must support 3P3W connection

Three phase four wire

Phase to neutral and phase to phase voltage

The meter must support 3P4W connection

Split supply or multiple incomers

Each supply point and connection type

One meter may not be enough

Generator and mains side by side

Which meter measures which source

Prevents mixed readings and unclear data labels


Do not just write “three phase meter”. State whether the system is three phase three wire or three phase four wire. If the neutral is present, say so. If the meter is measuring a generator output before an ATS, note that. If it is measuring the load side of an ATS, the meter may see either generator or mains depending on switch position.


State the nominal voltage


Voltage affects meter input selection and wiring. A useful specification gives the nominal voltage and the measurement points.


Examples include:


  • 230 V single phase

  • 400 V three phase four wire

  • 415 V three phase four wire

  • 480 V three phase three wire

  • Medium voltage system measured through voltage transformers


For low voltage systems, many panel meters can measure directly within their rated input range. Check the selected Acrel model data sheet before assuming direct connection is suitable.


For medium voltage or higher low voltage applications outside the meter’s direct input range, specify the voltage transformer ratio. For example, a system may use VTs to step voltage down to a safe metering input. The ratio must be entered into the meter so the displayed values match the real system.


Close-up view of voltage terminals and current transformer wiring inside a metering panel
Voltage and current inputs must match the system rather than the panel space.

Specify current measurement before choosing the meter


Current measurement is just as important as voltage. In many generator and mains installations, the meter reads current through external current transformers rather than by direct connection.


Choose the CT ratio carefully


The CT ratio should suit the maximum expected current, the generator rating, and the load profile. If the CT rating is far too high, low-load readings may lack useful resolution. If it is too low, the system may exceed the CT range.


A good specification names the CT ratio and secondary output.


Common examples include:


  • 100/5 A

  • 250/5 A

  • 400/5 A

  • 800/5 A

  • 1600/5 A

  • 250/1 A

  • 800/1 A


The meter must match the CT secondary, such as 1 A or 5 A. Do not leave this open. A meter ordered for 5 A CT inputs is not automatically correct for 1 A CTs.


Decide whether CTs are existing or new


This detail matters for supply and commissioning. Existing CTs may already feed another device. New CTs must suit the busbar or cable size and the installation space.


Include the following where possible:


  • CT ratio

  • CT secondary current

  • CT accuracy class if needed

  • CT type such as solid core, split core, or busbar mounted

  • Number of CTs

  • Whether CT shorting terminals are required

  • Whether CTs are dedicated to the new meter


If CTs are shared, take care. CT circuits should never be opened while energised. Any work on CT wiring should follow site safety rules and be done by competent personnel.


Match CT placement to the data required


The CT location decides what the meter actually measures. For generator and mains monitoring, placement can change the meaning of the readings.


CT position

What the meter sees

Common use

Generator output before breaker

Generator production only

Generator performance monitoring

Mains incomer

Utility import and export at the incomer

Grid supply monitoring

Load side of ATS

Load supplied from either source

Site load monitoring

Generator parallel bus

Combined generator contribution

Multi-set generator monitoring

Solar or battery connection point

Local generation or storage flow

Bidirectional energy tracking


A meter cannot infer where current is flowing if the CTs are installed in the wrong place. State the physical measuring point in the specification.


Decide what values need to be displayed and logged


Acrel meters are often selected to show live electrical values at the panel and send readings to a higher-level system. The right model depends on the required measurements.


Typical monitoring values include:


  • Voltage per phase

  • Current per phase

  • Frequency

  • Real power in kW

  • Apparent power in kVA

  • Reactive power in kVAr

  • Power factor

  • Imported energy in kWh

  • Exported energy in kWh where supported

  • Demand values where required

  • Total harmonic distortion if power quality information is needed


Not every project needs every value. A simple generator status panel may only need voltage, current, frequency, kW, and kWh. A site energy monitoring system may need import and export energy, demand, power factor, and communications.


Include bidirectional measurement when power can flow both ways


Bidirectional measurement is needed when energy can flow in both directions through the metering point. This is common on sites with embedded generation, battery storage, solar PV, grid export, or generator paralleling arrangements.


For a mains incomer, bidirectional measurement may be needed to separate:


  • Imported energy from the grid

  • Exported energy to the grid

  • Positive and negative power flow

  • Net energy where required by the monitoring platform


For a generator, bidirectional measurement may be relevant if there is a risk of reverse power or if the generator operates in parallel with another source. The meter can report the direction and size of power flow if the model and configuration support it. Protection against reverse power is a separate function and should not be assumed unless a suitable relay or controller is specified.


Use clear wording such as:


Meter shall support bidirectional active power and separate imported and exported energy registers for the selected metering point.

That is much clearer than saying “smart meter required”.


Eye-level view of a generator output panel with a digital meter showing electrical readings
Generator monitoring shows electrical performance without taking over generator control.

Confirm the auxiliary supply for the meter


The meter needs a power source for its electronics. This is separate from the measurement inputs, even where the same system voltage may be used.


Specify the auxiliary supply clearly. Common options may include AC or DC control supplies, depending on the chosen model. Do not assume the meter can be powered by any available voltage in the panel.


Useful details include:


  • Auxiliary supply voltage

  • AC or DC supply

  • Whether the supply is from mains, generator, UPS, battery, or control transformer

  • Whether the meter must remain powered when the generator is off

  • Whether monitoring is required during mains failure


This is especially important for generator monitoring. If the meter is powered only from the generator output, it may turn off when the generator stops. That may be acceptable for some panels, but not for sites that require communications or event visibility during standby periods.


For mains incomer monitoring, a meter powered from the same mains supply will usually turn off during a supply failure unless backed by UPS or another control supply. If the monitoring system must know that the mains has failed, the design may need a powered communications path and a suitable status input or relay elsewhere.


Choose communications early


Communications should be specified before the meter is ordered. The physical port, protocol, addressing, and data mapping all affect model selection and commissioning time.


Common requirements may include:


  • RS-485 communications

  • Modbus RTU

  • Ethernet communications

  • Modbus TCP where supported

  • Pulse output for energy counting

  • Digital input or output options where supported

  • Integration with BMS, SCADA, PLC, or an energy platform


The most common problem is incomplete wording. “Meter with comms” is not enough. State the protocol and connection type.


Better wording would be:


Meter shall provide RS-485 Modbus RTU communications for integration with the site BMS. Contractor shall provide network address, baud rate, parity, and register requirements before commissioning.

Or:


Meter shall provide Ethernet communications using a supported protocol suitable for connection to the site monitoring platform.

If the receiving system already exists, ask for its requirements. Some platforms expect specific registers, scaling, byte order, or data intervals. Acrel meters can often provide standard electrical data, but the integration team still needs the correct map for the selected model.


Plan the labels and data names


Generator and mains values must be easy to identify once they reach the monitoring system. Avoid vague device names such as `Meter 1` and `Meter 2`.


Use names that match the electrical drawing:


  • `Generator_Incomer_Meter`

  • `Mains_Incomer_Meter`

  • `ATS_Load_Side_Meter`

  • `Generator_1_Output`

  • `Utility_Import_Export`


Good naming reduces confusion during alarms, reporting, and maintenance.


Decide whether one meter or several meters are needed


Some projects try to use one meter for both generator and mains information. That is only suitable if the meter is installed at a point where it genuinely measures the required source or load.


Use separate meters when separate measurement points are required. For example, a generator incomer and a mains incomer are normally different physical points, so each may need its own meter and CT set.


Requirement

Likely metering approach

Monitor only total site load after ATS

One meter on the ATS load side

Monitor generator output and mains import separately

Two meters, one per source

Monitor several generator sets

One meter per set, or a defined metering point per generator

Monitor grid import and export

One bidirectional meter at the mains incomer

Monitor generator plus solar plus site load

Multiple meters at defined points


If cost is a concern, reduce the number of monitored points only after deciding which data can be lost. Do not assume one meter can report values from two different incomers unless the electrical arrangement makes that possible.


Overhead view of current transformers fitted around three phase conductors in a switchboard
The metering point defines whether readings belong to the generator, mains, or load.

Prepare a clear specification for ProSense Instruments


A good enquiry gives ProSense Instruments enough information to select the right Acrel meter and accessories without repeated back-and-forth questions. It does not need to be long, but it should be specific.


Use this checklist when preparing the request.


Project and application details


Include:


  • Generator monitoring, mains monitoring, or both

  • Number of metering points

  • Whether the meter is for panel display, remote monitoring, or both

  • Whether the installation is new or a retrofit

  • Any space limits in the panel

  • Indoor or outdoor panel environment if relevant


Electrical supply details


Include:


  • Single phase or three phase

  • Three wire or four wire arrangement

  • Nominal voltage

  • System frequency

  • Direct voltage measurement or VT ratio

  • Fault level or protection requirements if the panel builder needs them


Current measurement details


Include:


  • Maximum expected current

  • Generator or incomer rating

  • CT ratio

  • CT secondary output, usually 1 A or 5 A

  • CT type if required

  • Existing or new CTs

  • Metering point location


Measurement requirements


Include:


  • Voltage, current, frequency, kW, kVA, kVAr, power factor

  • kWh energy

  • Import and export energy if needed

  • Demand readings if needed

  • Harmonics or power quality values if needed

  • Any required alarm outputs or status signals, if supported by the selected meter


Communications requirements


Include:


  • No communications, local display only

  • RS-485 Modbus RTU

  • Ethernet or Modbus TCP where required and supported

  • Pulse output

  • BMS, SCADA, PLC, or energy platform connection

  • Baud rate, parity, address range, IP requirements, or site standards where known


Power supply and installation details


Include:


  • Auxiliary supply voltage

  • AC or DC auxiliary supply

  • Whether supply remains live during generator standby

  • DIN rail or panel mount preference

  • Required approvals or documentation

  • Any matching CTs, fuses, terminals, or accessories


Avoid the common selection mistakes


Most metering issues come from incomplete specifications rather than poor equipment. These are the problems to catch early.


Wrong wiring assumption


A three phase four wire meter configuration used on a three phase three wire system can give incorrect voltage and power readings. State the wiring arrangement.


Incorrect CT secondary


A 1 A CT and a 5 A meter input are not interchangeable. Match the meter to the CT secondary.


Unclear CT location


If the CTs are on the load side of an ATS, the meter measures the load, not the generator or mains source separately.


No bidirectional requirement stated


If import and export must be separated, specify bidirectional measurement and separate energy registers.


Communications added too late


A meter ordered without the right port or protocol may not connect to the site system. State communications at the buying stage.


Monitoring treated as control


A meter can support visibility, reporting, and analysis. It should not be expected to manage engine starting, breaker operation, synchronising, or protection unless those functions are provided by other specified devices.


A clear meter request saves time later


The best Acrel meter choice comes from a clear description of the electrical system and the data required. Before asking for a quotation, define the monitored point, voltage arrangement, CT details, auxiliary supply, communications method, and whether power flow is one-way or bidirectional.


For generator and mains monitoring, clarity matters more than a long specification. State what the meter must measure, where it will be installed, how it will be powered, and where the data must go. Keep generator control and protection as separate requirements. That gives ProSense Instruments the information needed to recommend a suitable Acrel metering solution and helps the finished system deliver readings that people can trust.


Comments


bottom of page